Home › Articles & guides › RCD TESTING PERTH: WHAT IS IT, WHO NEEDS IT AND HOW OFTEN?
Compliance
⏱ 6 min read
📅 Updated Apr 2026
Electricity Regulations WHS Act 2022
Home › Articles & guides › RCD TESTING PERTH: WHAT IS IT, WHO NEEDS IT AND HOW OFTEN?
Quick Answer If it plugs into a power point with a flexible cord, it generally needs to be test and tagged under the WHS Regulations 2022.
This guide explains what Perth Test and Tag Solutions (PTTS) tests, what is excluded, and how often testing if due, so you can give us accurate numbers for your quote.
Our standard electrical appliance testing to AS/NZS 3760:2022 measures key electrical parameters that indicate whether an appliance is, or has been, electrically compromised. Depending on the appliance, these tests include:
Earth Continuity
Insulation Resistance
Differential leakage
Polarity
Timed PRCD trip testing
Current leakage
Every appliance is also virtually inspected for any clear faults or electrical safety risks. The results for each appliance can be viewed in the test report provided on completion.
If it plugs into a power point with a flexible cord, it generally needs to be tested and tagged under the WHS Regulations 2022.
When one appliance needs two tests
In some circumstances one appliance may require two tests. This only happens when the appliance has a detachable lead. If the lead can be detached, AS/NZS 3760:2022 requires the lead and the appliance to each have their own individual test. The appliance test and the lead test are different types of tests and measure different parameters.
Common items with detachable leads include:*
*Not all appliances in this list have detachable leads. It varies a lot depending on the make, model and design of each appliance.
If required, PTTS can also take care of the rest of your compliance in the same visit.
Extinguishers, hose reels, fire blankets, and smoke alarms
Not sure about an item? Include it in your count and our technician will confirm on the day.
Under AS/NZS 3760, the retest interval depends on your industry and how hard the equipment is used.
| Interval | Environment |
|---|---|
| 3 months | Mining, construction, demolition and building sites, or any workplace that falls within AS/NZS 3012 |
| 6 months | Warehouses, workshops, commercial kitchens, production |
| 12 months | Offices, meeting rooms, staff kitchens, shop floors, front counters |
| 24 months | Hotels, hostels, boarding houses and residential accommodation |
| 60 months | Server rooms, comms racks, security systems and fixed office equipment not prone to flexing or damage |
Construction and demolition sites follow AS/NZS 3012, with a coloured tag for each quarter:
If you have any questions on the day, please let our friendly technicians know. We will work through and explain any questions or queries that come up.